Load profile - example
For coolers equipped with two wetting pumps.
Please click:   
Achieving conservation excellence is mainly dependant on an intelligent control system, especially for multiple unit installations. Our  controls all parallel in one cooling loop installed hybrid dry coolers in a very efficient way. Algorithms are configured to maximize the operation time in dry mode, thus saving a maximum amount of water.
Remember, especially for AC installations the IPLV standard is weighting the 100% load point only with 1%, means a chiller is operating throughout the year with 100% load only to 1% of it`s operating time. Major operation time due to chiller load is around 75% and 50% while these points are weighted with 42% resp. 45%. See table sheet below:
IPLV definition 1998 standard
%Load   WC ECWT 
°F
 AC EDB 
°F
 EC EWB 
°F
 Weighting
100%8595 75.00  1%
 75%7580 68.7542%
 50%6565 62.5045%
 25%6555 56.2512%